Search In this Thesis
   Search In this Thesis  
العنوان
Enhancing the performance of combined cycle power plants through intake air cooling /
الناشر
Anas Abdelmotaleb Ali Mostafa ,
المؤلف
Anas Abdelmotaleb Ali Mostafa
هيئة الاعداد
باحث / Anas Abdelmotaleb Ali Mostafa
مشرف / Mahmoud A. Fouad
مشرف / Taher M. Halawa
مشرف / karam mahmoud hassan elshazly
تاريخ النشر
2018
عدد الصفحات
136 P. :
اللغة
الإنجليزية
الدرجة
الدكتوراه
التخصص
الهندسة الميكانيكية
تاريخ الإجازة
3/9/2018
مكان الإجازة
جامعة القاهرة - كلية الهندسة - Mechanical Power Engineering
الفهرس
Only 14 pages are availabe for public view

from 162

from 162

Abstract

A technical and economical study of the effects of entry air cooling on the performance of combined cycle power plants is performed. Thermodynamic model was developed to simulate the combined cycle before and after the integration to the proposed cooling systems. Direct data are collected from the plant. The results show that the total electric energy increase is 190,228 MWh/year and the net cash flow 2.64 MUS$/year when using the mechanical system while the corresponding values of the absorption system are 181,994 MWh/year and the net cash flow 2.38 MUS$/year